What is the RCD (Residual Current Device / RCCB(Residual Current Circuit Breaker)
https://engrtechnologies.blogspot.com/2014/03/what-is-rcd-residual-current-device.html
What
is the
RCD (Residual Current Device / RCCB(Residual Current
Circuit Breaker)
CHARACTERISTICS
Limitation of RCCB
RCD (Residual Current Device / RCCB(Residual Current
Circuit Breaker)
CHARACTERISTICS
·
Phase (line) and Neutral both
wires connected through RCD.
·
It trips the circuit when there is earth
fault current.
·
The amount of current flows through the
phase (line) should return through neutral .
·
It detects by RCD. any mismatch between two
currents flowing through phase and neutral detect by -RCD and trip the circuit
within 30Miliseconed.
·
If a house has an earth system connected to
an earth rod and not the main incoming cable, then it must have all circuits
protected by an RCD (because u mite not be able to get enough fault current to
trip a MCB)
·
RCDs are an extremely effective form of
shock protection
The most widely used are 30 mA (milliamp) and 100 mA
devices. A current flow of 30 mA (or 0.03 amps) is sufficiently small that it
makes it very difficult to receive a dangerous shock. Even 100 mA is a
relatively small figure when compared to the current that may flow in an earth
fault without such protection (hundred of amps)
A 300/500 mA RCCB may be used where only fire protection
is required. eg., on lighting circuits, where the risk of electric shock is
small.
Limitation of RCCB
·
Standard
electromechanical RCCBs are designed to operate on normal supplywaveforms and cannot be guaranteed to operate where none standard
waveforms are generated by loads. The most common is the half wave rectified
waveform sometimes called pulsating dc generated by speed control devices, semi
conductors, computers and even dimmers.
·
Specially modified RCCBs are available which
will operate on normal ac and pulsating dc.
·
RCDs
don’t offer protection against current overloads: RCDs detect an imbalance in the live and neutral
currents. A current overload, however large, cannot be detected. It is a
frequent cause of problems with novices to replace an MCB in a fuse box with an
RCD. This may be done in an attempt to increase shock protection. If a
live-neutral fault occurs (a short circuit, or an overload), the RCD won’t
trip, and may be damaged. In practice, the main MCB for the premises will
probably trip, or the service fuse, so the situation is unlikely to lead to
catastrophe; but it may be inconvenient.
·
It is now possible to get an MCB and and RCD
in a single unit, called an RCBO (see below). Replacing an MCB with an RCBO of
the same rating is generally safe.
·
Nuisance
tripping of RCCB: Sudden
changes in electrical load can cause a small, brief current flow to earth,
especially in old appliances. RCDs are very sensitive and operate very quickly;
they may well trip when the motor of an old freezer switches off. Some
equipment is notoriously `leaky’, that is, generate a small, constant current
flow to earth. Some types of computer equipment, and large television sets, are
widely reported to cause problems.
·
RCD
will not protect against a socket outlet being wired with its live and neutral
terminals the
wrong way round.
·
RCD
will not protect against the overheating that results when conductors are not properly screwed into
their terminals.
RCD will not protect against live-neutral shocks, because the current in the live and neutral is
balanced. So if you touch live and neutral conductors at the same time (e.g.,
both terminals of a light fitting), you may still get a nasty shock.